Lesson 7 of 9 · about 18 minutes
The Fire Record: Notable BESS Fires and Where the List Lives
You'll be able to
- Describe the major BESS incidents by date, place, size, chemistry and outcome
- Find and use EPRI's BESS Failure Incident Database and know what it counts and excludes
- Explain how a falling failure rate per GWh and a rising count of incidents can both be true
- State the strongest points on both sides of the failure-rate debate
Every battery hearing ends up at the same place: somebody holds up a photo of Moss Landing and somebody else holds up a chart showing failure rates falling off a cliff. Both are real. This lesson gives you the record behind each, starting with the incidents and then the database most people are quoting without having opened.
Notable incidents
Unless noted, size, chemistry, enclosure and outcome come from EPRI's BESS Failure Incident Database as downloaded in October 2026. Sizes are MW / MWh; a dash means EPRI lists no figure.
| Date | Place | Size | Chemistry, enclosure | Outcome |
|---|---|---|---|---|
| 2017 to 2019 | South Korea | Many sizes | Mostly lithium-ion, mixed | 28 incidents in EPRI's table for those three years; the government recommended shutting down at-risk systems |
| Apr. 19, 2019 | Surprise (McMicken), Ariz. | 2 / 2 | NMC, outdoor container | Internal cell defect; clean agent could not stop propagation; deflagration when the door was opened; four firefighters seriously injured (UL FSRI) |
| Sept. 15, 2020 | Liverpool, England | 20 / 10 | NMC, outdoor | Explosion before responders were called; limited to one of three containers; declared over two days later |
| Apr. 16, 2021 | Beijing, China | - / 25 | LFP, outdoor | Explosion killed two firefighters, injured one; one employee unaccounted for |
| July 30, 2021 | Moorabool, Victoria, Australia | 300 / 450 | NMC, outdoor Megapacks | During commissioning; service mode shut off telemetry, cooling and protection; fire spread to a second unit |
| Apr. 18, 2022 | Chandler, Ariz. | 10 / 40 | NMC, indoor | Declared out May 1, about 13 days |
| Sept. 20, 2022 | Moss Landing, Calif. (PG&E Elkhorn) | 182.5 / 730 | NMC, outdoor Megapacks | One Megapack burned |
| May 31, 2023 | East Hampton, N.Y. | 5 / 40 | NMC, indoor | Roads closed, train service stopped about an hour; internal sprinklers contained it |
| June 26, 2023 | Warwick, N.Y. (two sites) | 8 / 8.2 and 4 / 22 | LFP, outdoor | Failures at two new sites within 24 hours during a storm; explosion at one |
| July 27, 2023 | Chaumont, N.Y. | 5 / 15 | NMC, outdoor | Shelter in place within 1 mile |
| Sept. 18, 2023 | Valley Center, Calif. | 140 / 560 | NMC, outdoor | One container; second incident at this site |
| Oct. 2, 2023 | Melba, Idaho (Idaho Power substation) | 2 / 8 | LFP, outdoor | Allowed to burn out over several days; roads closed; county air tests in normal range (KIVI) |
| May 15, 2024 | Otay Mesa, San Diego (Gateway) | 250 / 250 | NMC cells, indoor | High hydrogen kept a 600-foot barrier for 22+ hours; shelter order and evacuation warning; reignited several times; fire department left about 17 days later |
| Sept. 5, 2024 | Escondido, Calif. | 30 / 120 | NMC, outdoor | One of 24 containers; evacuation within about a quarter mile; classes canceled at some schools |
| Jan. 16, 2025 | Moss Landing, Calif. (Vistra Moss Landing 300) | 300 / 1,200 | NMC, indoor | Monitor-and-contain; evacuation orders; two roads and a highway closed; about 55% of roughly 100,000 modules damaged and about 56,000 burned (EPA); flared again Feb. 18, 2025 |
| Feb. 19, 2025 | Tilbury, England | 300 / 600 | LFP, outdoor | Site under construction; one container; water curtain kept it from spreading; out a day later |
| Aug. 30, 2025 | Parkfield, Calif. (California Flats) | 60 / 240 | NMC, outdoor Megapacks | Four of 84 units damaged; five homes within 2 miles evacuated; allowed to burn out |
| Dec. 19, 2025 | Warwick, N.Y. (Church Street) | 4 / 17.9 | LFP, outdoor | One container; site fully charged at the time, SOC cut to 50% afterward; three days of air monitoring |
| Sept. 7, 2026 | Summerside, Prince Edward Island | 10 / 20 | Lithium-ion, outdoor | Thermal activity about two weeks; shelter instructions, voluntary evacuation within 500 m, school closures |
| Sept. 18, 2026 | Moss Landing, Calif. (cleanup) | Damaged modules left in the burned building | NMC, indoor | About 1,300 modules burned during cleanup; shelter in place within one-third mile until about 4:15 p.m. (EPA) |
| Sept. 22, 2026 | La Verne, Calif. | 0.5 / - | Lithium-ion, outdoor | Explosion in one of two containers; one employee hurt during evacuation; road and school closures |
A few patterns stand out. The worst human toll came early: Arizona in 2019 and Beijing in 2021, both explosions that hit firefighters. The largest environmental event, Moss Landing in 2025, was an older NMC system packed into a building. Recent fires at modern outdoor sites have mostly stayed in one or a few units, yet still brought evacuations, shelter orders, school closures and days of smoldering. And Idaho has its own entry.
Where the list lives
The list most people mean is EPRI's BESS Failure Incident Database. It used to live on EPRI's Storage Wiki, and the old storagewiki.epri.com database page now redirects to the Energy Storage Hub. EPRI's methodology page says:
- It began in 2021, after the South Korean fires and the Arizona explosion, and includes incidents back to 2011.
- The main table tracks utility-scale and commercial and industrial systems. A second table tracks other incidents: manufacturing, transport, storage and recycling. Residential systems are not tracked.
- Its focus is incidents with wider public health and safety impact, not routine operational failures.
- Entries come from media reports and public documents such as root cause reports and press releases, found through searches of English-language media, keyword alerts and verified crowdsourcing, with translated local-language reports for some Taiwan and South Korea incidents. EPRI says it cannot guarantee every incident is captured, especially before 2018 and 2019.
- Source documents are archived, and the whole table can be downloaded.
- It was renamed from "Failure Event" to "Failure Incident" to match emergency response language.
As downloaded in October 2026, the stationary table had 165 rows. Thirty-two are placeholders that name only a country and year, for incidents EPRI knows about without public detail. Of the rows with locations, South Korea had 56 and the U.S. 37. Nineteen rows are flagged as explosions.
This is a research database, not a reporting system. Inclusion depends on someone writing about the incident, and two-thirds of the incidents EPRI tried to classify in 2024 lacked enough public information to name a cause. States are filling gaps on their own. After three fires in summer 2023, New York formed an Inter-Agency Fire Safety Working Group, which released draft recommendations on February 6, 2024 for lithium-ion systems over 600 kWh, covering peer review of permit applications, emergency response planning, local fire department training and updates to the state fire code. New York adopted energy storage code updates based on that work on July 25, 2025, and the 2025 New York State Fire Code that carries them took effect December 31, 2025, according to NYSERDA.
The failure-rate claim
EPRI compares incidents to the cumulative capacity deployed. Its database page says the rate per cumulative deployed capacity dropped 99 percent from 2018 to 2025, and that its graph includes 33 non-public incidents. EPRI's October 2026 report, Risk Factors and Failure Statistics of Lithium-Ion BESS, put the drop at 98 percent; Energy-Storage.news updated its coverage after EPRI clarified that figure. The May 2024 version of the analysis found a 97 percent drop from 2018 to 2023. The 2026 report also found failure rates now comparable to large oil-filled transformers, that 93 percent of recorded utility-scale incidents caused no injuries or deaths, and that no incident spread beyond the facility perimeter.
Meanwhile the yearly count of incidents in the public table has not fallen much: 17 rows dated 2018, 30 in 2023, 26 in 2024 and 23 in 2025.
Worked example: both numbers are true
Use the public counts and ask what the 98 percent claim implies.
Rate = incidents / cumulative GWh deployed
Rate 2025 / Rate 2018 = 0.02 (a 98% drop)
(23 / C2025) / (17 / C2018) = 0.02
(23 / 17) x (C2018 / C2025) = 0.02
1.35 x (C2018 / C2025) = 0.02
C2025 / C2018 = 1.35 / 0.02 = about 68
So the claim requires cumulative deployment to have grown roughly 68-fold from 2018 to 2025, which is the scale of the buildout. This check is rough, because EPRI's own calculation uses its full list including non-public incidents. The point holds: each battery is far less likely to fail than one built in 2018, and there are many more batteries, so incidents keep happening.
Reading the debate fairly
The industry case rests on that rate, on EPRI's finding that newer vintages fail less, on the move away from big indoor installations, and on the absence of U.S. injuries or deaths since 2019. It is a strong case about the fleet.
Residents and opponents make several points. The database depends on public reporting, so it likely undercounts. Most causes are unknown. A per-GWh rate describes the fleet, not the consequences for the people living next to the one site that fails, and evacuations, school closures and multi-day smoldering keep happening at modern sites. Some argue the rate is flattered because the denominator is full of new systems that have not had time to age into failure. EPRI's data cuts against that last point: it found failure rates fall with age, and 72 percent of failures with known age happened in the first two years. So young fleets tend to fail more, not less.
Where the evidence points: the improvement is real and large, the database is incomplete, and a falling rate does not answer the local question of what happens, and who pays, when this particular site is the one in the table next year.
Common mix-ups
- Claim: Battery fires are getting more common. What the evidence shows: Counts are roughly flat to higher, but the rate per GWh deployed fell about 98 percent from 2018 to 2025.
- Claim: If an incident isn't in EPRI's database, it didn't happen. What the evidence shows: EPRI says it may miss incidents with little or local-only coverage, and it does not track home batteries.
- Claim: Modern outdoor sites don't have serious incidents. What the evidence shows: Escondido 2024, Parkfield 2025 and Summerside 2026 all brought evacuations or shelter orders, though fires stayed in a few units.
Reporting angle
- Download EPRI's table and filter by the cell maker and integrator named in a local application.
- For any local incident, request the fire district's incident report, dispatch logs, air monitoring results and any after-action review under the Idaho Public Records Act.
- Ask the operator whether it reported the incident to EPRI and whether a root cause analysis will be released.
- When a developer cites the 98 percent figure, ask for its own fleet's incident history, not the industry's.
- When opponents cite Moss Landing, check whether the proposed project is indoor or outdoor, NMC or LFP, and how its spacing compares.
Research angle
- The database, methodology and download: EPRI BESS Failure Incident Database.
- Gateway incident coverage: Batteries and Energy Storage Technology magazine, May 2024.
- Melba coverage: KIVI, October 2023.
- Moss Landing official timeline: EPA updates page.
- The 2026 risk factor report coverage: Energy-Storage.news.
- New York's state response: NYSERDA, Inter-Agency Fire Safety Working Group.
Check yourself
1. Where is the most widely cited public list of grid battery failures maintained?
EPRI started the database in 2021 and now hosts it at energystorage.epri.com; the old storagewiki address redirects there.
2. Which kinds of systems does EPRI's main incident table track?
The stationary table covers utility and C&I failures worldwide; a second table covers manufacturing, transport, storage and recycling incidents; residential failures are not tracked.
3. What was distinctive about the Gateway fire in Otay Mesa that began May 15, 2024?
EPRI's event page records the building enclosure, the 600-foot barrier for more than 22 hours, repeated reignition and the roughly 17-day response.
4. What happened at an Idaho Power substation near Melba in October 2023?
EPRI lists the October 2, 2023 incident; KIVI reported the sheriff's office said the recommended response was to let it burn out completely.
5. EPRI's public table shows 17 incidents dated 2018 and 23 dated 2025, yet EPRI reports the failure rate per deployed GWh fell about 98 percent. Using only those public counts, roughly how much must deployed capacity have grown for the rate to fall 98 percent?
Rate ratio = (23/17) / growth = 0.02, so growth = 1.35 / 0.02 = about 68. EPRI's own figure also counts 33 non-public incidents, so this is only a rough check.
6. Which statement about EPRI's database is accurate?
EPRI says it relies on public reporting and cannot guarantee it captures every incident.
Terms in this lesson
- EPRI
- The Electric Power Research Institute, a nonprofit research organization funded largely by utilities.
- BESS Failure Incident Database
- EPRI's public list of stationary battery failure incidents worldwide, with size, chemistry, age, enclosure and sources for each.
- Failure rate per deployed GWh
- Incidents in a year divided by the cumulative battery capacity installed, a measure of fleet risk.
- Reignition
- A fire restarting in damaged cells after it appeared to be out.
- Shelter in place
- An order to stay indoors with windows and doors shut and ventilation off until the hazard passes.
Sources
- EPRI, Battery Energy Storage System Failure Incident Database (Energy Storage Hub; methodology and downloadable stationary table) checked 2026-10
- EPRI Storage Wiki, Failure Event: USA, CA, San Diego, 15 May 2024 checked 2026-10
- UL FSRI, Report: Four Firefighters Injured in Lithium-Ion Battery Energy Storage System Explosion, Arizona (July 2020) checked 2026-10
- KIVI, Battery fire at Idaho Power substation south of Melba continues to burn (Oct. 3, 2023) checked 2026-10
- U.S. EPA, Moss Landing Vistra battery fire response page and updates (including Sept. 18, 2026 fire) checked 2026-10
- U.S. EPA news release, EPA oversees largest lithium-ion battery cleanup in agency history at Moss Landing (Sept. 29, 2025) checked 2026-10
- Energy-Storage.news, Global BESS failure rates declined 98% between 2018 and 2025 (EPRI report, Oct. 8, 2026) checked 2026-10
- Energy-Storage.news, Battery storage failure incident rate dropped 97% between 2018 and 2023 (May 16, 2024) checked 2026-10
- BEST Magazine, San Diego's Gateway Energy Storage lithium-ion BESS fire reignites (updated May 20, 2024) checked 2026-10
- NYSERDA, New York Inter-Agency Fire Safety Working Group (code adoption July 25, 2025; 2025 NYS Fire Code effective Dec. 31, 2025) checked 2026-10
- EPRI, Insights from EPRI's BESS Failure Incident Database: Analysis of Failure Root Cause (May 2024) checked 2026-10
- NYSERDA, Governor Hochul releases initial recommendations from Inter-Agency Fire Safety Working Group (Feb. 6, 2024) checked 2026-10