Lesson 6 of 9 · about 18 minutes
Failure Modes and Thermal Runaway: Heat, Gas, Fire and Explosion
You'll be able to
- List the main triggers of battery failure: electrical, thermal, mechanical, internal defect and environmental
- Describe the steps of thermal runaway and propagation from cell to cell
- Explain why accumulated off-gas creates explosion risk and how venting and ventilation reduce it
- Summarize what EPRI's root cause analysis found about why and when systems fail
Most battery failures start small: one cell, one connection, one leak. Whether that ends as a smoking cabinet, a container that burns for hours or a blast that throws firefighters across a yard depends on what happens in the next few minutes inside the enclosure. That chain is what codes, designs and fire tactics are trying to break.
What sets a cell off
| Trigger type | Examples | What guards against it |
|---|---|---|
| Electrical abuse | Overcharge, overdischarge, external short circuit, arcing in DC wiring | BMS limits, fuses, contactors, ground fault detection |
| Thermal abuse | Cooling failure, hot weather, a neighboring fire | HVAC or liquid cooling, BMS derating, spacing, barriers |
| Mechanical abuse | Crush or puncture in shipping or installation, seismic shaking, vibration | Handling procedures, seismic design, inspection at receipt |
| Internal defect | Contaminants, separator flaws, lithium plating that grows dendrites | Factory quality control; the BMS can only watch for symptoms |
| Environmental | Rain or condensation inside enclosures, humidity, dust | Enclosure sealing, humidity control, drainage |
| Balance-of-system faults | Coolant leaks, suppression leaks, inverter or transformer failure | Design review, commissioning tests, maintenance |
Inside thermal runaway
Sandia's handbook describes the core problem: a cell operated outside its limits can make heat faster than it can shed it, and once a metal-oxide cathode gets hot it releases oxygen while the organic electrolyte supplies fuel. The steps below are simplified; real cells overlap them.
Propagation is the step that turns one bad cell into a plant fire. Module barriers try to keep heat inside one cell or module. Spacing and walls try to keep a fire inside one rack or container. Codes now ask manufacturers to prove, by test, how far a failure spreads; lesson 8 covers UL 9540A and large-scale fire testing.
What comes out
Failing cells vent a mix of gases and particles. The 2024 Journal of Energy Storage review of 60 studies found the average gas mix similar across LFP and NMC, with more hydrogen from LFP and more carbon monoxide from NMC. Larsson and colleagues, in a 2017 Scientific Reports study burning seven types of commercial lithium-ion cells, measured hydrogen fluoride at 20 to 200 milligrams per watt-hour of battery capacity, plus 15 to 22 mg/Wh of phosphoryl fluoride in some tests. The Arizona hazmat team in 2019 measured dangerous levels of hydrogen cyanide and carbon monoxide inside the container's hot zone, per UL FSRI.
| Gas | Why it matters |
|---|---|
| Hydrogen | Very flammable, wide flammable range; the main explosion driver in many enclosures |
| Carbon monoxide | Flammable and toxic |
| Methane, ethylene and other hydrocarbons | Flammable |
| Carbon dioxide | Displaces oxygen in closed spaces |
| Hydrogen fluoride, phosphoryl fluoride | Toxic and corrosive; from the fluorinated salt in the electrolyte |
| Hydrogen cyanide | Toxic; measured at Surprise, Arizona in 2019 |
| Metal-bearing particles | Can carry nickel, cobalt and manganese from NMC cathodes; lesson 9 covers Moss Landing |
Fire or explosion
When vented gas ignites as it comes out, the result is a fire: hot, smoky, long, but without a pressure blast. When gas pours into a closed enclosure and does not ignite right away, it mixes with air. If the mix reaches its flammable range and then finds a spark, hot surface or flame, it deflagrates. That is the pattern in the worst incidents in EPRI's database.
- Surprise, Arizona, April 19, 2019. Clean agent discharged; gas built for about three hours; the door was opened and about three minutes later the container deflagrated. Four firefighters seriously injured.
- Beijing, April 16, 2021. A 25 MWh LFP system exploded; two firefighters died and a third was injured, with one employee unaccounted for.
- Aghione, Corsica, April 6, 2023. Shortly after doors were opened, an explosion injured two firefighters; three more were hospitalized for smoke.
- Isa, Kagoshima, Japan, March 27, 2024. Firefighters opened the door and the explosion came when they tried to use the smoke exhaust system; four were injured.
- Gunwi, South Korea, January 17, 2022. An explosion occurred ten minutes after firefighters left the structure; no injuries.
Of the 165 rows in EPRI's stationary table as of September 2026, 19 are flagged as explosions. Most incidents are fires without a blast, and EPRI's October 2026 report found 93 percent of recorded utility-scale incidents caused no injuries or deaths, with no reported U.S. BESS injuries or deaths since the 2019 Arizona event.
How designs control explosions
Prevention keeps gas below its flammable range with detection and exhaust ventilation; NFPA 69 is the standard. Venting lets the blast happen safely: panels that open under pressure and point the force upward, away from people and other units; NFPA 68 is the standard. Many systems use both. Sandia notes that active suppression can make gas buildup worse, because gas that is not burning accumulates, which is why gas detectors for carbon monoxide and hydrogen have been added. The 2026 NFPA 855 adds a unit-level test with intentional ignition of vent gases when cell or module tests release flammable gas.
Worked example: how little gas it takes
Take an invented walk-in container with 60 cubic meters of open air space. Use the lower flammability limits from the 2024 review: 6.2 percent for LFP off-gas, 7.9 percent for NMC.
Off-gas volume that reaches the LFL:
LFP: 60 m3 x 0.062 = 3.72 m3
NMC: 60 m3 x 0.079 = 4.74 m3
A ventilation design limited to 25% of the LFL
(the 2018 IFC ventilation target):
LFP: 3.72 x 0.25 = 0.93 m3
NMC: 4.74 x 0.25 = 1.19 m3
Ratio: 3.72 / 4.74 = 0.78
From the LFL alone, LFP gas makes this box
flammable with about 22% less gas than NMC gas.
A few cubic meters is about the volume of a small closet. That is why opening a door on a container full of unlit off-gas is the moment of greatest danger, and why firefighters now try to read gas levels remotely before going near.
Why systems fail: the root cause data
EPRI, TWAICE and Pacific Northwest National Laboratory classified incidents in EPRI's database by root cause (design; manufacturing; integration, assembly and construction; operation) and by failed element (cell or module, controls, balance of system). Their May 2024 white paper found:
- Only 26 of 81 incidents had enough public information to classify.
- Integration, assembly and construction was the most common root cause, about 10 of the 26 by Utility Dive's count. Manufacturing was the least common.
- Cells and modules were the failed element in 3 of the 26; controls and balance-of-system parts made up most of the rest.
- 72 percent of failures with known system age happened during construction, commissioning or the first two years of operation.
The incident record fits that picture: the Moorabool, Australia fire happened during commissioning; the Tilbury, England fire in February 2025 happened while the site was still under construction; the two Warwick, New York failures in June 2023 hit new systems during a large storm. EPRI's October 2026 report added that failure rates fall with system age and with newer vintages, and recommended safety reviews and retrofits of early-vintage systems.
The data has a real limit: two-thirds of incidents could not be classified because the public record was too thin. Neighbors of a failed site often never learn the cause.
Common mix-ups
- Claim: Battery systems explode all the time. What the evidence shows: 19 of 165 incidents in EPRI's table are flagged as explosions. Most incidents are fires, and 93 percent of utility-scale incidents caused no injuries.
- Claim: When the smoke stops, the danger is over. What the evidence shows: Damaged cells can reignite days or weeks later; Gateway reignited several times and Moss Landing flared again on February 18, 2025.
- Claim: Suppression systems make batteries safe. What the evidence shows: Stopping flames without removing gas can set up a deflagration, as at Surprise in 2019.
Reporting angle
- Ask what gases the site detects, at what alarm levels, and whether readings are available to firefighters remotely before entry.
- Ask whether enclosures use explosion prevention (NFPA 69), deflagration venting (NFPA 68) or both, and request the engineering report.
- Ask for the commissioning plan and who witnesses commissioning tests, given that 72 percent of known-age failures are early-life.
- Ask what the emergency plan says about opening doors, and who has authority to decide.
- After any incident, ask for the root cause analysis and whether it will be public. Most never are.
Research angle
- Thermal runaway mechanics and detection: Sandia Handbook Chapter 3.
- The fluoride gas measurements: Larsson et al., Scientific Reports (2017).
- The explosion that changed fire service practice: UL FSRI Arizona report.
- Root causes: EPRI root cause white paper (2024).
- Explosion and injury entries: EPRI BESS Failure Incident Database.
Check yourself
1. Why did the 2019 Surprise, Arizona incident end in an explosion rather than an open fire?
UL FSRI's timeline shows the alarm and clean agent discharge at about 4:55 p.m., the door opened about 8:01 p.m., and the deflagration about 8:04 p.m.
2. At about what temperature range do conventional polyolefin separators melt, shorting a cell internally?
Sandia's handbook gives 130 to 170 degrees Celsius for conventional polyolefin separators.
3. Which gases did the Arizona hazmat team find at dangerous levels before the deflagration?
FSRI reports the team measured dangerously high hydrogen cyanide and carbon monoxide during entries into the hot zone.
4. In EPRI's 2024 root cause analysis, what share of failures with known system age happened during construction, commissioning or the first two years of operation?
EPRI found 72 percent were early-life failures, which is why commissioning quality and early inspections matter.
5. Under the 2018 IFC, when ventilation is required for a battery room, it must keep flammable gas below what level?
The 2018 IFC's battery room ventilation provision sets 25 percent of the LFL, or for hydrogen 1.0 percent of the room volume.
6. EPRI's October 2026 report found what share of recorded utility-scale incidents caused no injuries or fatalities?
Energy-Storage.news reported 93 percent of recorded utility-scale incidents caused no injuries or deaths.
Terms in this lesson
- Thermal runaway
- A self-heating chain reaction in a cell: heat drives reactions that make more heat, ending in venting, fire or both.
- Propagation
- Thermal runaway spreading from one cell to its neighbors, then module to module and unit to unit.
- Off-gas
- The mix of gases a cell vents in failure, including hydrogen, carbon monoxide, carbon dioxide, hydrocarbons and fluorine compounds.
- Deflagration
- A fast-burning gas ignition that moves slower than sound but builds pressure; the explosion type seen in battery enclosures.
- Explosion control
- Design measures that either keep gas below flammable levels (ventilation, NFPA 69) or release blast pressure safely (venting panels, NFPA 68).
- Early-life failure
- A failure during construction, commissioning or the first years of operation, often from installation or integration errors.
Sources
- Sandia National Laboratories, DOE-OE Energy Storage Handbook, Chapter 3: Lithium-ion Batteries checked 2026-10
- UL FSRI, Report: Four Firefighters Injured in Lithium-Ion Battery Energy Storage System Explosion, Arizona (July 2020) checked 2026-10
- Larsson et al., Toxic fluoride gas emissions from lithium-ion battery fires, Scientific Reports 7, 10018 (2017) checked 2026-10
- pv magazine USA, How safe are LFP batteries? (Apr. 10, 2024) checked 2026-10
- EPRI, Insights from EPRI's BESS Failure Incident Database: Analysis of Failure Root Cause (May 2024) checked 2026-10
- Utility Dive, Cells and modules not responsible for most battery energy storage system failures (May 21, 2024) checked 2026-10
- Energy-Storage.news, Global BESS failure rates declined 98% between 2018 and 2025 (EPRI report, Oct. 8, 2026) checked 2026-10
- EPRI, BESS Failure Incident Database (stationary storage table, Sept. 2026 update) checked 2026-10
- 2018 International Fire Code as adopted in Idaho, Section 1206 (UpCodes viewer) checked 2026-10
- MeyerFire, What's new in NFPA 855, 2026 edition (Sept. 2025) checked 2026-10