Lesson 7 of 9 · about 18 minutes
Cooling options and water use
You'll be able to
- Compute a reactor's waste heat from its thermal and electric ratings
- Compare water withdrawal and consumption for each cooling method using published medians
- Estimate a plant's annual water use in gallons and acre-feet
- Explain the output and cost penalty of dry cooling and why arid sites still consider it
A nuclear plant is a steam engine with an unusual fire. The reactor makes heat, the turbine turns some of it into electricity, and everything else has to go somewhere. For a typical water-cooled reactor that "everything else" is about two thirds of the heat. The cooling system is how a plant throws it away, and the method chosen decides most of the plant's water footprint.
For data center cooling, which stacks on top of this when a reactor serves a campus, see the data center cooling lesson and the data center water lesson.
Waste heat first
Example: how much heat leaves the plant
- A light-water SMR sending out 300 MWe at 33 percent efficiency makes 300 ÷ 0.33 ≈ 909 MWt.
- Waste heat: 909 minus 300 = 609 MW, around the clock.
- A microreactor like eVinci, 15 MWt and 5 MWe, rejects 15 minus 5 = 10 MW.
So the small reactor rejects about 1/60 of the waste heat of the 300 MWe unit. That difference is why some microreactor developers plan to reject heat to air, while 300 MWe plants mostly plan on water.
Hotter reactors convert heat more efficiently, so they reject a bit less per megawatt-hour. But no design escapes the problem. A helium-cooled Xe-100 or a sodium-cooled Natrium uses gas or metal to carry heat out of the core, and then still needs a heat sink on the power side. "Gas-cooled" describes the core, not the plant's water use.
The cooling methods
The difference between withdrawal and consumption matters more than any other point in this lesson. A once-through plant pulls enormous volumes but sends most of it back, warmer. A cooling tower pulls much less but evaporates a large share of what it takes. In a river basin where every acre-foot is already claimed, consumption is what hurts other users.
The numbers
The standard reference is NREL's 2011 review by Jordan Macknick and colleagues, which compiled published estimates for each technology and cooling type. Medians, in gallons per megawatt-hour of electricity:
| Plant and cooling | Withdrawal (gal/MWh) | Consumption (gal/MWh) |
|---|---|---|
| Nuclear, cooling tower | 1,101 | 672 |
| Nuclear, once-through | 44,350 | 269 |
| Nuclear, pond | 7,050 | 610 |
| Coal (generic), cooling tower | 1,005 | 687 |
| Gas combined cycle, cooling tower | 253 | 198 |
| Gas combined cycle, dry cooling | 2 | 2 |
| Utility-scale solar PV | 26 | 26 |
| Wind | 0 | 0 |
Gas combined cycle plants use less water than nuclear because about two thirds of their power comes from a gas turbine that needs no steam cooling. The NREL data predates any SMR, so treat the nuclear rows as a guide for water-cooled SMRs, not as measured SMR values. Designs that run hotter should land somewhat lower per MWh. No one has measured an operating U.S. SMR yet.
A real example: Kemmerer Unit 1
The NRC's final environmental impact statement for TerraPower's Natrium plant in Wyoming (NUREG-2268, October 2025) says the plant would use a mechanical draft cooling tower. Raw water would come from the Naughton Power Plant's raw water settling basin, which draws from the Hams Fork River, through a new pipeline of about 6 miles. Average demand is listed at 3,689 gallons per minute, maximum 5,270.
Example: Kemmerer's water in yearly terms
- Minutes in a year: 60 × 24 × 365 = 525,600.
- 3,689 gal/min × 525,600 ≈ 1.94 billion gallons a year at average demand.
- 1,939,000,000 ÷ 325,851 gallons per acre-foot ≈ 5,950 acre-feet a year.
- Electricity: 345 MWe × 8,760 hours × 0.91 capacity factor ≈ 2.75 million MWh.
- Water per MWh: 1,939,000,000 ÷ 2,750,000 ≈ 705 gallons per MWh withdrawn.
That is below the 1,101 gal/MWh median for towered nuclear plants. Be careful with it, though. The EIS demand figure is withdrawal; the share actually evaporated was not given in the section reviewed for this lesson. And the plant can boost to 500 MWe from stored heat at times, which changes the per-MWh math. Ask for the consumption figure before quoting a single number.
Dry cooling and its penalty
Dry cooling rejects heat to air through big finned coils, the way a car radiator does. Water use drops to almost nothing. The cost is efficiency: air is a worse heat sink than evaporating water, especially on hot afternoons, so the turbine can't extract as much work. NREL's review cites national-average annual output penalties for switching from wet to dry cooling of 6.8 percent for nuclear, 1.7 percent for gas combined cycle and 6.9 percent for other fossil steam plants. Dry systems also cost more to build and take more land.
Example: the price of saving water
An invented 300 MWe water-cooled SMR near the town of Lone Butte, running at a 91 percent capacity factor:
- Annual output with a wet tower: 300 × 8,760 × 0.91 ≈ 2,391,000 MWh.
- Water consumed at the 672 gal/MWh median: 2,391,000 × 672 ≈ 1.61 billion gallons, or about 4,930 acre-feet a year.
- Output lost with dry cooling at 6.8 percent: 2,391,000 × 0.068 ≈ 162,600 MWh a year.
- At an invented wholesale value of $60 per MWh: 162,600 × $60 ≈ $9.8 million a year in lost sales, before the higher construction cost.
Put another way, saving roughly 4,900 acre-feet costs about $2,000 per acre-foot per year in lost power at these assumptions ($9.8 million ÷ 4,930). Whether that is a bargain depends on what water is worth in that basin. In much of the arid West it can be.
Hybrid systems split the difference: dry most of the year, wet sections on the hottest days. They are a common compromise for arid sites. When a developer says a design "can use" dry cooling, ask whether this site will, and what output figure the economics assume.
Water rights in the West
In Idaho and most western states, a new plant can't simply pump water. It needs a water right, usually by buying and transferring an existing one, under prior appropriation rules where older rights are served first in shortages. The prior appropriation lesson explains the system, and new claims from data centers and energy covers how large new users fit in. A 5,000 acre-foot consumptive need is a large transfer in any basin. Intake structures on rivers and lakes also fall under Clean Water Act section 316(b), which regulates how cooling water intakes affect fish.
Common mix-ups
- Claim: Gas-cooled or sodium-cooled SMRs don't use water. What the evidence shows: The core coolant isn't water, but waste heat must still be rejected. Kemmerer's Natrium plant plans a wet cooling tower.
- Claim: Once-through plants use the most water. What the evidence shows: They withdraw the most. Cooling towers consume more per MWh because they evaporate it.
- Claim: Dry cooling is free. What the evidence shows: It costs output (about 6.8 percent a year for nuclear on national averages) and capital.
Reporting angle
- Ask which cooling system the site will use, not which ones the design allows. Then ask for withdrawal and consumption in acre-feet per year, average and peak.
- Ask where the water right comes from. Search the state water agency (in Idaho, the Idaho Department of Water Resources) for transfer or new appropriation applications by the developer or a related company.
- In the NRC environmental document, find the water use and hydrology sections and the cumulative impact discussion for the basin.
- If the plant will serve a data center, add the data center's own cooling water to the total.
- Ask what happens to output and to the plant's contract price on the hottest days if it uses dry or hybrid cooling.
Research angle
- NREL water factors review (Macknick et al., 2011), tables 1 to 3.
- NUREG-2268, Kemmerer EIS, sections on water use and hydrology.
- EPA cooling water intake (316(b)) page.
- Idaho Department of Water Resources for water right searches and transfer applications.
- USGS acre-foot explainer for unit conversions.
Check yourself
1. A reactor makes 900 MWt and sends out 300 MWe. How much heat must it reject?
900 minus 300 = 600 MW of waste heat, which goes to water, air or both.
2. Per NREL's review (Macknick and others, 2011), what is the median water consumption of a nuclear plant with a recirculating cooling tower?
672 gal/MWh consumed, with 1,101 gal/MWh withdrawn. Once-through cooling withdraws about 44,350 but consumes about 269.
3. Which cooling method withdraws the most water but consumes less of it?
Once-through systems pass huge volumes through the condenser and return most of it, warmer, to the river, lake or sea.
4. The NRC's environmental impact statement for Kemmerer Unit 1 lists an average water demand of 3,689 gallons per minute. About how many acre-feet is that per year?
3,689 × 525,600 minutes ≈ 1.94 billion gallons; ÷ 325,851 gallons per acre-foot ≈ 5,950 acre-feet.
5. Using national averages, NREL's review cites an annual output penalty of about what for switching a nuclear plant from wet to dry cooling?
The report cites 6.8 percent for nuclear, 1.7 percent for gas combined cycle and 6.9 percent for other fossil steam plants.
6. An Xe-100 is cooled by helium. Does the plant need water?
Helium cools the core. The power conversion side still rejects heat, and that heat sink is where water use comes from.
Terms in this lesson
- Withdrawal
- Water taken from a source. Some or most may be returned.
- Consumption
- Water withdrawn and not returned, mostly lost to evaporation.
- Once-through cooling
- Pulling water from a river, lake or sea, passing it through the condenser once and returning it warmer.
- Recirculating (wet) cooling tower
- A tower that cools condenser water by evaporating part of it, then reuses the rest. Low withdrawal, high consumption.
- Dry cooling
- Rejecting heat to air through finned coils or air-cooled condensers, using almost no water but lowering efficiency, especially on hot days.
- Acre-foot
- The volume of water that covers one acre one foot deep: 325,851 gallons.
Sources
- NREL: A Review of Operational Water Consumption and Withdrawal Factors for Electricity Generating Technologies (Macknick, Newmark, Heath, Hallett, NREL/TP-6A20-50900, March 2011) checked 2026-10
- NRC: NUREG-2268, Environmental Impact Statement for Kemmerer Power Station Unit 1 (Oct. 2025) checked 2026-10
- NRC: NUREG-2268 full text (PDF) checked 2026-10
- NEI Magazine: eVinci in criticality test (15 MWt / 5 MWe) checked 2026-10
- EIA: U.S. nuclear industry (91 percent capacity factor in 2025) checked 2026-10
- EPA: Cooling water intakes, Clean Water Act section 316(b) checked 2026-10
- USGS: Water science school, acre-foot conversion checked 2026-10