Lesson 6 of 9 · about 17 minutes
Cooling: Air, Water and Liquid to the Chip
You'll be able to
- Explain why nearly all data center electricity ends up as heat
- Describe hot/cold aisle containment and the ASHRAE recommended temperature range
- Compare evaporative, chilled water, dry cooler, direct-to-chip and immersion systems on water and power
- Estimate cooling water use from a facility's energy and WUE
Almost every watt that goes into a server comes out as heat. A 100 MW data hall is, from a physics point of view, a 100 MW space heater that happens to compute along the way. Cooling is the job of moving that heat from the chip, out of the building, and into the outdoor air or a body of water. Every method makes a trade between electricity and water, and the right choice depends on climate, rack density and what the local water supply can bear.
How hot is too hot?
ASHRAE, the engineering society that publishes the standard thermal guidelines for IT equipment, recommends server inlet air between 18 and 27 degrees C (about 64 to 81 degrees F). It also defines wider "allowable" ranges; Class A1 equipment can run from 15 to 32 degrees C. Older data centers were kept chilly, around 20 degrees C or lower, out of habit. Running warmer saves cooling energy, and most modern sites run near the top of the recommended range.
Air cooling and aisles
Servers pull air in the front and blow it out the back. If racks all faced the same way, each row would breathe the previous row's exhaust. So rows face each other: fronts together make a cold aisle, backs together make a hot aisle. Adding doors and a roof to one aisle, called containment, keeps the streams from mixing and lets the cooling system work with warmer supply air.
Air has a limit. It carries little heat per unit volume, so cooling a 100 kW rack with air alone would take a hurricane of fans. In practice, air cooling tops out somewhere around 30 to 50 kW per rack, even with containment and rear-door heat exchangers. Past that, liquid has to come closer to the chip.
Getting the heat outdoors
Inside the hall, heat moves into air or liquid. Outside, it has to leave the site. The main options:
| Heat rejection method | How it works | Water use on site | Electricity use | Best climate |
|---|---|---|---|---|
| Direct or indirect evaporative cooling | Outside air is cooled by evaporating water, directly or across a heat exchanger | High in hot, dry weather; near zero in cool weather | Low | Dry climates |
| Water-cooled chillers with cooling towers | Chillers cool a water loop; towers evaporate water to dump the chillers' heat | High, year round | Moderate | Most climates, where water is available |
| Air-cooled chillers | Chillers reject heat through fans and coils, no evaporation | Very low | Higher, especially on hot days | Water-scarce areas |
| Dry coolers (free cooling) | Fans blow outdoor air across coils carrying warm coolant; no compressor when outside air is cool enough | Very low | Low when cool outside, needs backup on hot days | Cool climates, or warm-water liquid cooling anywhere |
| Outside air economizer | Filtered outside air goes straight into the hall when conditions allow | None (or a little for humidity) | Very low | Cool, clean-air climates |
Liquid to the chip
Direct-to-chip cooling bolts a metal cold plate onto each processor. Coolant flows through it, picks up heat right where it is made, and returns to a coolant distribution unit, which hands the heat to the building's water loop. Nvidia's newest rack designs run almost entirely on this approach, with coolant entering at up to about 45 degrees C. Warm coolant is the quiet breakthrough: water that leaves the racks well above outdoor temperatures can often be cooled by plain outdoor air, without chillers and without evaporating water.
Immersion cooling drops whole servers into tanks of non-conductive fluid. Single-phase immersion circulates the fluid through a heat exchanger. Two-phase immersion uses a fluid that boils at a low temperature and condenses on coils. Immersion is common in crypto mining (Riot Platforms' Rockdale, Texas site uses both immersion and air cooling) and is growing in some AI and HPC deployments, but it requires special servers and handling, and some two-phase fluids face scrutiny over PFAS chemistry.
Water: direct and indirect
A data center uses water two ways. Direct water is what the site itself consumes, mostly through evaporation in cooling. Indirect water is consumed at power plants generating the site's electricity, mostly through steam cycle cooling at thermal plants. Lawrence Berkeley National Laboratory estimated that U.S. data centers directly consumed about 17 billion gallons in 2023, and that indirect water tied to their electricity was roughly 12 times larger. Its scenarios had direct use possibly doubling, or even quadrupling, by 2028. Indirect water depends on the local grid mix: wind and solar use almost none, thermal plants use a lot.
Companies are moving away from evaporative cooling in water-stressed places. Microsoft reported a fleet average water usage effectiveness of 0.30 liters per kWh in fiscal 2024, down from 0.49 in 2021, and said all new designs since August 2024 use closed-loop cooling that is filled once and recirculated, avoiding more than 125 million liters a year per datacenter. Its Fairwater AI campus in Wisconsin uses closed-loop liquid cooling. The trade-off, which Microsoft acknowledged, is somewhat higher electricity use, which it described as nominal across the fleet.
Worked example: one campus, two cooling choices
The invented Coyote Basin campus runs 50 MW of IT load all year.
- Yearly IT energy: 50,000 kW times 8,760 hours = 438,000,000 kWh
- With evaporative cooling at a WUE of 1.8 L/kWh: 438,000,000 times 1.8 = 788,400,000 liters, about 788 million liters (about 208 million gallons, at 3.785 liters per gallon)
- With a closed loop at a WUE of 0.05 L/kWh (humidification and small losses): 438,000,000 times 0.05 = 21,900,000 liters, about 22 million liters
Now the electricity side. Suppose the closed loop raises PUE from 1.20 to 1.28. Grid energy goes from 438,000,000 times 1.20 = 525.6 million kWh to 438,000,000 times 1.28 = 560.6 million kWh, an extra 35 million kWh a year. Whether that is a good trade depends on local water stress and what the extra power plant output uses in water and emissions. The WUE figures here are illustrative; ask for the real design numbers.
| Cooling approach | Rack density it handles | Site water | Cooling power |
|---|---|---|---|
| Room air, no containment | Up to about 5 to 10 kW | Depends on heat rejection | Highest per kW of IT |
| Air with hot or cold aisle containment | Up to about 20 to 30 kW | Depends on heat rejection | Moderate |
| Rear-door heat exchangers | About 30 to 50 kW | Depends on heat rejection | Moderate |
| Direct-to-chip liquid | 100 kW and up | Can be near zero with warm water and dry coolers | Low (fans shrink, chillers often avoided) |
| Immersion | 100 kW and up | Can be near zero | Low |
Common mix-ups
- Claim: Liquid-cooled data centers must use more water. What the evidence shows: Liquid to the chip usually runs in a closed loop. Whether a site consumes much water depends on how heat leaves the building. Liquid at the chip does not answer that question.
- Claim: "Zero water" means no water at all. What the evidence shows: It usually means zero water evaporated for cooling. Restrooms, kitchens, humidification and the initial fill still use water, and the power plants supplying the site use water too.
- Claim: Data center water goes back to the river. What the evidence shows: Evaporated water leaves as vapor. Some systems discharge a portion as blowdown to the sewer. Ask for both consumption and discharge.
Reporting angle
- Ask the developer which cooling system the site will use, its design WUE, and its peak-day water demand in gallons per day, not just the annual average.
- Request the water service agreement with the city or water district, and any well permits or water right applications filed with the state water agency.
- Ask whether blowdown goes to the municipal sewer and whether the wastewater plant has the capacity.
- Ask what happens on the hottest days: does the site switch to evaporative mode, and how much more water does that use?
Research angle
- ASHRAE 2021 thermal guidelines: Temperature and humidity envelopes for equipment.
- Microsoft zero-water cooling post: Company claims and WUE figures to check against.
- Latitude Media on the water footprint: How power generation adds to a site's water use.
- LBNL 2024 report, full text: Full report with the assumptions on power, cooling and water.
- 2CRSi power and cooling guide: Rack power and cooling by chip generation.
- Microsoft on Fairwater: The company's own description of its Wisconsin AI site.
Check yourself
1. What is ASHRAE's recommended inlet air temperature range for most data center IT equipment?
ASHRAE's thermal guidelines recommend 18 to 27 degrees C (about 64 to 81 degrees F) at the equipment inlet, with wider allowable ranges for some classes.
2. Which cooling approach usually uses the most water on site?
Evaporative systems cool by evaporating water, which leaves the site as vapor. Closed loops with dry coolers or air-cooled chillers use little water but more electricity in hot weather.
3. In hot aisle/cold aisle layout, how are racks arranged?
Facing rows front to front makes a cold aisle; back to back makes a hot aisle. Containment walls or roofs keep the two air streams from mixing.
4. Microsoft reported a fleet average WUE of 0.30 liters per kWh in fiscal 2024. How much water is that for 1,000,000 kWh of IT energy?
1,000,000 kWh times 0.30 L/kWh = 300,000 liters.
5. What is the main trade-off when a site switches from evaporative cooling to closed-loop mechanical cooling?
Evaporation is an efficient way to reject heat. Replacing it with chillers saves water but makes compressors work harder. Microsoft described the energy increase in its fleet as nominal.
6. Why do AI racks above about 50 kW generally need liquid cooling?
Water holds roughly 3,500 times more heat per unit volume than air. Above a few tens of kilowatts, the fans and airflow needed become impractical.
Terms in this lesson
- Hot aisle/cold aisle
- A layout where racks face each other so cool intake air and hot exhaust air stay in separate aisles.
- Containment
- Doors, panels or roofs that enclose a hot or cold aisle to stop the air streams mixing.
- Evaporative cooling
- Cooling by evaporating water into air, which removes heat but consumes water.
- Chilled water plant
- Chillers that cool water, which is piped to air handlers or coolant units in the halls.
- Direct-to-chip liquid cooling
- Coolant pumped through cold plates mounted on processors, carrying heat away from the hottest parts directly.
- Immersion cooling
- Submerging servers in a non-conductive fluid that absorbs heat.
Sources
- ASHRAE: 2021 Thermal Guidelines reference card (recommended and allowable envelopes) checked 2026-10
- Microsoft: Sustainable by design, next-generation datacenters consume zero water for cooling (Dec. 9, 2024) checked 2026-10
- Microsoft: Inside the world's most powerful AI datacenter (Fairwater cooling) checked 2026-10
- Latitude Media: Data centers' hidden water footprint is linked to the grid (LBNL water figures) checked 2026-10
- LBNL: 2024 United States Data Center Energy Usage Report checked 2026-10
- 2CRSi: Nvidia from Blackwell to Rubin, power and cooling guide checked 2026-10
- Riot Platforms: Rockdale facility (immersion and air cooling) checked 2026-10