Lesson 3 of 9 · about 19 minutes
Solar PV: Cells, Inverters, Rooftops and Fields
You'll be able to
- Explain how a photovoltaic cell, a panel and an inverter work together
- Compute a solar array's annual output from its size and capacity factor, and compare regions
- Explain DC versus AC ratings and why the difference changes the numbers
- Describe net metering, net billing and export credits, and find the commission case behind a local change
A solar panel has no moving parts. Light goes in, current comes out. That simplicity is why solar went from a rounding error to the largest source of new U.S. generating capacity: EIA counted 30.8 GW of utility-scale solar added in 2024, 27.2 GW in 2025, and 43.4 GW planned for 2026, about half of everything developers expected to build that year.
What happens inside a cell
A silicon solar cell is a thin wafer with two layers. One is "doped" with atoms that leave spare electrons; the other with atoms that leave gaps where electrons could go. Where the layers meet, an electric field forms. When a photon of sunlight hits the silicon with enough energy, it knocks an electron loose. The field pushes that electron one way and the gap it left the other. Put metal contacts on both faces, connect a wire, and you have a current.
The physics sets a ceiling. Photons with too little energy pass through or warm the cell. Photons with too much waste the excess as heat. For a single silicon junction the theoretical limit is roughly 30 percent of the sunlight's energy. Commercial panels sold today convert roughly a fifth or a bit more. Heat also hurts: a cell gets less efficient as it warms, so a cold, clear spring day can beat a scorching July afternoon.
From cell to grid
Dozens of cells (commonly 60 or 72, or twice that many half-cut cells) are wired into a panel. Panels are wired into strings. Strings feed an inverter, which turns DC into AC, matches the grid's 60-cycle rhythm and, under modern interconnection rules, can help hold voltage steady. Utility plants use central or string inverters by the hundreds; homes use one string inverter or a small microinverter on each panel.
The DC versus AC trap
Developers often install more panel capacity than inverter capacity. A plant might have 120 MW of panels (DC) feeding 100 MW of inverters (AC), a DC-to-AC ratio of 1.2. On bright middays the inverters cap output and a little energy is "clipped," but in mornings, evenings and cloudy hours the plant runs closer to its AC limit for longer. When you see a solar number, ask which rating it is. A press release that says 120 MW and a utility filing that says 100 MW may describe the same project.
Utility-scale versus rooftop
| Utility-scale | Rooftop (residential) | |
|---|---|---|
| Typical size | 5 to several hundred MW | Around 5 to 10 kW per home |
| Mounting | Ground racks, usually single-axis trackers | Fixed to the roof at whatever angle the roof has |
| Cost per watt | Low, from bulk purchasing and simple installation | Several times higher: permits, ladders, sales, small scale |
| Output per kW | Higher (tracking, ideal tilt) | Lower (shading, roof direction, fixed tilt) |
| Main benefit argued | Cheap energy at scale | Uses existing roofs, no new land or long lines, customer control |
| Main criticism argued | Land use, transmission needs | Higher cost per kWh, cost shifting under some billing rules |
Small-scale solar is a bigger slice than many people assume. EIA estimated about 74 billion kWh from small-scale PV in 2023, on top of 165 billion kWh from utility-scale solar.
Capacity factor by region
The sun sets the budget. EIA's national utility-scale PV fleet ran at about 23.2 percent in 2023 and 2024 and 24.4 percent in 2025. Idaho's fleet ran at about 25 percent each year from 2022 through 2024. Lazard's 2026 regional analysis used 18 percent for the Midcontinent grid (MISO), 19 percent for the Southwest Power Pool and 27 percent for California.
Worked example: same plant, two places
An invented developer, Sunfield Partners, builds identical 100-MW (AC) plants in two regions.
Desert plant at 27%: 100 x 8,760 x 0.27 = 236,520 MWh per year
Midwest plant at 18%: 100 x 8,760 x 0.18 = 157,680 MWh per year
Difference: 78,840 MWh, the desert plant makes 50% more
Build costs are similar, so the cost per MWh in the Midwest is roughly half again as high. That one ratio explains much of why solar costs differ by state.
A rooftop example: a 7-kW home system at a 16 percent capacity factor makes 7 x 8,760 x 0.16 = about 9,800 kWh a year. That is a fair chunk of a typical home's use, but most of it arrives between 9 a.m. and 4 p.m.
Land use
Solar farms take a lot of ground. Exact acreage depends on panel efficiency, spacing between tracker rows, terrain and setbacks, so take the number from the project's own filings rather than a national rule of thumb. Suppose our invented Sunfield project fences 600 acres for 100 MW. That is 6 acres per MW. At 27 percent capacity factor, each acre yields about 394 MWh a year (236,520 / 600).
The tradeoffs are real on both sides. Opponents point to lost cropland, changed views and habitat fragmentation; supporters note that a farm can lease land for steady income, that grazing sheep under panels ("agrivoltaics") is common, and that land can return to cropping after a 30- to 35-year project life if the decommissioning bond is good. In irrigated farm country, a less discussed question is water rights: does the lease retire them, sell them, or hold them?
Net metering: why the arguments never end
When rooftop solar makes more than the house is using, the extra flows onto the grid. The billing rule for that export is a fight in nearly every state.
- Classic net metering: the meter spins backward. Each exported kWh offsets a purchased kWh at the full retail rate, which includes the cost of poles, wires and customer service.
- Net billing: exports are measured in real time and credited at an export rate, usually tied to the utility's avoided cost of energy, which can vary by season and hour.
The utility argument: retail rates bundle in fixed grid costs, so paying full retail for exports lets solar owners skip their share of the grid, shifting costs to neighbors without panels. The solar side: exports have extra value the utility does not count (avoided line losses, reduced peak demand, lower emissions), and changing the rules after people invested is unfair. Both sides commission "value of solar" studies, and their answers depend heavily on what values they include.
In December 2022 the California Public Utilities Commission adopted decision D.22-12-056, a net billing tariff for customers who applied to interconnect on or after April 15, 2023. In Idaho, the Public Utilities Commission issued Order No. 36048 on December 29, 2023, in case IPC-E-23-14, approving Idaho Power's move to real-time net billing with an export credit rate. The commission said on-site generation should offset a customer's own use, avoid cost shifting, and pay a fair value for exports. News coverage at the time counted 846 public comments, about half opposing the change; systems installed before December 20, 2019 were grandfathered.
The federal incentive changed too. The 2025 tax law, Public Law 119-21, ended the 30 percent residential clean energy credit (section 25D) for expenditures after December 31, 2025. The cost lesson of this module covers the commercial credits.
Common mix-ups
- Claim: Solar panels don't work in cold or northern places. What the evidence shows: Cold helps cell efficiency. What hurts is fewer sun hours and low winter sun angle. Germany and the northern U.S. run large fleets at lower capacity factors.
- Claim: Net metering is a subsidy, full stop, or a fair trade, full stop. What the evidence shows: It depends on how a state values exports and on how many customers have solar. Value studies reach different answers because they include different benefits and costs. Ask whose study it is.
- Claim: A 100-MW solar farm is equal to a 100-MW gas plant. What the evidence shows: Same nameplate, very different output: roughly a quarter of the hours versus whatever the gas plant is dispatched for, and solar's output is zero at night.
Reporting angle
- For a utility-scale project: the county permit, the fenced acreage, the AC and DC ratings, the decommissioning plan and bond, and the interconnection queue position.
- For rooftop policy: find the case number at the state utilities commission. Read the utility's application, the staff comments and the final order. Count public comments yourself.
- Ask the utility how many net-metered customers it has, the total installed kW, and how it calculates the export credit.
- Ask homeowner-facing installers how they quote savings after the 25D credit ended. Check whether quotes still assume the old credit.
Research angle
- EIA Electric Power Monthly, Table 6.7.B: Solar PV capacity factors.
- EIA Idaho electricity profile: Idaho solar capacity and generation.
- Lazard LCOE+: Cost and firming tables for solar.
- CPUC, Net Billing Tariff: California's rooftop solar credit rules for comparison.
- EIA FAQ on small-scale solar: Estimates of rooftop generation.
- RSM summary of federal clean energy credit changes: What changed for solar incentives.
Check yourself
1. What does an inverter do in a solar system?
Panels make DC. Homes and the grid run on AC at a fixed frequency, so the inverter converts and synchronizes it.
2. A 100-MW (AC) solar farm runs at a 25 percent capacity factor. About how much does it produce in a year?
100 x 8,760 x 0.25 = 219,000 MWh.
3. Lazard's 2026 firming analysis used which approximate solar capacity factors for MISO and CAISO?
Lazard's regional table used 18 percent for MISO in the Midwest and 27 percent for sunny California.
4. Under the 2025 federal tax law (Public Law 119-21), what happened to the 25D residential clean energy credit for homeowners?
The law ended the 25D credit for expenditures made after 2025. Under the earlier law it ran through 2032 before phasing down.
5. What is the main difference between classic net metering and 'net billing' tariffs like Idaho Power's and California's?
Classic net metering lets exports spin the meter backward at the full retail rate. Net billing measures exports in real time and credits them at an export rate, often based on avoided cost.
6. A solar project is described as '120 MWdc / 100 MWac.' Which number should you use with a capacity factor that EIA reports on an AC basis?
Match the bases. EIA's utility-scale figures are on AC net capacity, so use the 100-MW AC rating.
Terms in this lesson
- Photovoltaic (PV) cell
- A semiconductor device, usually silicon, that turns light directly into direct current electricity.
- Inverter
- Electronics that convert DC from panels into grid-synchronized AC.
- Single-axis tracker
- A rack that rotates rows of panels east to west during the day to follow the sun.
- DC-to-AC ratio
- Panel capacity divided by inverter capacity. Ratios above 1 squeeze more hours of full output from the inverters.
- Net metering
- A billing rule where a customer's exported solar offsets their purchases at the full retail rate.
- Net billing
- A billing rule that credits exported solar at a separate export rate rather than the retail rate.
Sources
- EIA, Electric Power Monthly Table 6.7.B, solar PV capacity factor 2023 to 2025 checked 2026-10
- EIA, Idaho Electricity Profile 2024, state data tables (Tables 4A, 5, 15) checked 2026-10
- Lazard, 2026 Levelized Cost of Energy+ (Version 19.0), cost of firming intermittency regional table checked 2026-10
- EIA Today in Energy, record capacity additions planned for 2026 (Feb. 20, 2026) checked 2026-10
- Idaho Public Utilities Commission news release, Order No. 36048, Case IPC-E-23-14 (Dec. 29, 2023) checked 2026-10
- Idaho Capital Sun via Yahoo News, Hundreds opposed changes to rooftop solar credits in Idaho checked 2026-10
- California Public Utilities Commission, Net Billing Tariff (D.22-12-056) checked 2026-10
- RSM, Tax bill significantly changes clean energy credits and incentives (OBBBA summary) checked 2026-10
- EIA, Electricity in the U.S. FAQ (small-scale solar estimate, 2023) checked 2026-10